Fire Alarm and Life Safety

Non-power Limited Plenum

Shielded

Non-power Limited Plenum Fire Alarm Cable
Approvals:





Applications:


Temperature:

Voltage:

Conductor:

Insulation:

Shield:


Jacket:


Color Code:
UL Type NPLFP
UL Subject 1581
UL Subject 1425
NEC Article 760-17
California State Fire Marshal

Fire & Burglar Alarms, Control Circuits, Intercoms, Detection/Monitor

-20°C to 75°C

150 Volt

Annealed Bare Copper

Halar

Aluminum Mylar Foil
Tinned Copper Drain Wire

Red Plenum PVDF
Ripcord

Color Code V

 

Cross Section

Specifications
Part Number Conductor Number of
Conductors
Insulation
(Type, Thickness)
Nominal Jacket
Thickness
Nominal O.D. Nominal Capacitance
Weight (lbs) Per Mft.
pF/ft* pF/ft.**
IP122SNPL 12 AWG
Solid BC
1.59 Ω/MFT
2 Halar, .020" .010" .263" 35 64 68
IP142SNPL 14 AWG
Solid BC
2.52 Ω/MFT
2 Halar, .020" .010" .230" 31 56 46
IP162SNPL 16 AWG
Solid BC
4.1 Ω/MFT
2 Halar, .020" .010" .205" 27 49 34
IP182SNPL 18 AWG
Solid BC
6.2 Ω/MFT
2 Halar, .020" .010" .184" 24 43 26

Additional Notes:
Other Jacket Colors Available - 25,000 ft. Minimum Order Require
*Capacitance Between Conductors
**Capacitance Between One Conductor and the Other Connected to the Shield

Go Back to Short Specifications Product Category Go Back to Products Main Page Part Number Index

While every effort is made to insure that the product specifications are current and accurate, they are subject to change without notification. Please contact Isotec for specification verification if required.