Process Control Cable

300 Volt Power Limited Tray Cable (PLTC)

Multi-conductor Overall Braid Shield

Data Grade - Plenum - Shielded
Approvals:



Applications:



Temperature:

Voltage:

Conductor:

Insulation:

Shield:

Jacket:


Color Code:
UL Type CL3, FPL, PLTC
UL Subject 13, 1424, 1581
California State Fire Marshal

Low Voltage Industrial Controls, Power Limited Fire Alarm, Power Limited Circuits, Power Limited Tray Cable

-20°C to 105 °C

300 Volt

Annealed Bare Copper

PVC & Nylon

85% Tin Copper Braid

Gray PVC
Ripcord

Color Code Y

 

Cross Section

Specifications
Part Number Conductor
(Type, DCR)
Number of
Conductors
Insulation
(Type, Thickness)
Nominal Jacket
Thickness
Nominal O.D. Nominal Capacitance
Weight (lbs) Per Mft.
pF/ft* pF/ft.**
I182BPLTC 18 AWG
7/26 BC
6.2 Ω/MFT
2 PVC, .015"
Nylon, .005"
.035" .238" 61 110 44
I183BPLTC 18 AWG
7/26 BC
6.2 Ω/MFT
3 PVC, .015"
Nylon, .005"
.035" .284" 61 110 53
I184BPLTC 18 AWG
7/26 BC
6.2 Ω/MFT
4 PVC, .015"
Nylon, .005"
.035" .300" 61 110 26

Additional Notes:
Other Jacket Colors Available - 25,000 ft. Minimum Order Required
*Capacitance Between Conductors
**Capacitance Between One Conductor and the Other Connected to the Shield

Go Back to Short Specifications Product Category Go Back to Products Main Page Part Number Index