| Part Number | Conductor (Type, DCR) |
Number of Pairs |
Insulation (Type, Thickness) |
Nominal Jacket Thickness |
Nominal O.D. | Nominal Capacitance pF/ft* |
Weight (lbs) Per Mft. |
|---|---|---|---|---|---|---|---|
| I161PRPLTC | 16 AWG 19/29 BC 4.1 Ω/MFT |
1 | PVC, .012" | .035" | .230" | 33.3 | 41 |
| I162PRPLTC | 16 AWG 19/29 BC 4.1 Ω/MFT |
2 | PVC, .012" | .040" | .232" | 33.3 | 78 |
| I164PRPLTC | 16 AWG 19/29 BC 4.1 Ω/MFT |
4 | PVC, .010" | .050" | .450" | 33.3 | 13 |
| I181PRPLTC | 18 AWG 7/26 BC 6.4 Ω/MFT |
1 | PVC, .010" | .035" | .218" | 31.7 |
30 |
| I182PRPLTC | 18 AWG 7/26 BC 6.4 Ω/MFT |
2 | PVC, .010" | .040" | .260" | 31.7 | 57 |
| I184PRPLTC | 18 AWG 7/26 BC 6.4 Ω/MFT |
4 | PVC, .010" | .042" | .390" | 31.7 | 99 |
| I186PRPLTC | 18 AWG 7/26 BC 6.4 Ω/MFT |
6 | PVC, .010" | .035" | .420" | 31.7 | 139 |
| I201PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
1 | PVC, .010" | .040" | .203" | 29.5 | 23 |
| I202PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
2 | PVC, .010" | .040" | .300" | 29.5 | 46 |
| I204PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
4 | PVC, .010" | .035" | .345" | 29.5 | 68 |
| I206PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
6 | PVC, .010" | .040" | .435" | 29.5 | 102 |
| I208PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
8 | PVC, .010" | .050" | .465" | 29.5 | 123 |
| I2010PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
10 | PVC, .010" | .050" | .545" | 29.5 | 151 |
| I2012PRPLTC | 20 AWG 7/28 BC 10.2 Ω/MFT |
12 | PVC, .010" | .050" | .555" | 29.5 | 172 |
Additional Notes:
Other Jacket Colors Available - 25,000 ft. Minimum Order Required
*Capacitance Between Conductors

While every effort is made to insure that the product specifications are current and accurate, they are subject to change without notification. Please contact Isotec for specification verification if required.