SIMTRA™ Power Cable

SIMTRA Ferrite Barrier Power Cable

Multi-conductor TC Power Cables

Multi-conductor TC Power Cable
Approvals:



Applications:




Temperature:

Voltage:

Conductor:

Insulation:

Barrier:

Jacket:
UL Listed Type TC, NEC Article 340
UL Subject 1277
UL Subject 83 THHN Conductors

Networking, Telecommuncations, Audio & Video, A/C Control, Fire Alarm Systems, Security, Lighting Control, P.S.S. and Kiosks, and
Touch screen Systems

90°C Dry or 75°C Wet

600 Volt

Stranded Bare Copper

PVC with Nylon

Ferrite

Sunlight Resistant, Oil Resistant and Direct Burial PVC

Cross Section

Specifications
Part Number Gage Insulation
(Type, Thickness)
Barrier
(Type, Thickness)
Jacket Conductors
+ Ground
Jacket
Thickness
Overall O.D. Weight (lbs)
Per Mft.
16_FTC 16 AWG
(19 x .0119)
PVC, .016”
Nylon, .005”
Ferrite, .022" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.045"
.045"
.045"
.045"
.337"
.362"
.391"
.425"
99
111
123
135
14_FTC 14 AWG
(19 x .0147)
PVC, .016”
Nylon, .005”
Ferrite, .022" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.045"
.045"
.045"
.045"
.371"
.399"
.432"
.468"
136
159
184
209
12_FTC 12 AWG
(19 x .0185")
PVC, .016”
Nylon, .005”
Ferrite, .022" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.045"
.045"
.045"
.060"
.418"
.452"
.522"
.557"
140
171
203
235
10_FTC 10 AWG
(19 x .0231")
PVC, .020”
Nylon, .005”
Ferrite, .022" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.045"
.060"
.060"
.060"
.513"
.554"
.603"
.646"
273
326
381
436
08_FTC 8 AWG
(19 x .0295")
PVC, .020”
Nylon, .005”
Ferrite, .025" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.060"
.060"
.060"
.060"
.643"
.635"
.761"
.825"
339
400
490
566
06_FTC 6 AWG
(19 x .0372")
PVC, .020”
Nylon, .005”
Ferrite, .025" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.060"
.060"
.080"
.080"
.725"
.789"
.885"
.980"
480
597
716
872
04_FTC 4 AWG
(19 x .0469")
PVC, .040”
Nylon, .006”
Ferrite, .028" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.060"
.080"
.080"
.080"
.924"
1.006"
1.101"
1.199"
714
871
1087
1277
02_FTC 2 AWG
(19 x .0591")
PVC, .040”
Nylon, .006”
Ferrite, .028" PVC 2 + 1
3 + 1
4 + 1
5 + 1
.080"
.080"
.080"
.080"
1.055"
1.153"
1.266"
1.382"
1007
1273
1560
1830

Additional Notes:
Underscore in part number designates total number of conductors (Conductors + Ground) 3, 4, 5, or 6.

Go Back to Short Specifications Product Category Go Back to Products Main Page Part Number Index

While every effort is made to insure that the product specifications are current and accurate, they are subject to change without notification. Please contact Isotec for specification verification if required.